The AEMC INSTRUMENTS GroundFlex Field Kit Model 6474 is a flexible-loop ground-testing system for measuring earth-ground resistance in towers without disconnection.
The GroundFlex® Field Kit Model 6474 is a comprehensive tower ground resistance testing system designed for power transmission, cellular, windmill, and other towers. It combines the Model 6472 ground tester with the advanced Model 6474 GroundFlex® Adapter to enable testing of energized towers with one to four legs without disconnecting the overhead ground wire. Features include flexible sensors wrapped around tower legs for high-sensitivity measurements, comprehensive testing capabilities (Fall-of-Potential, soil resistivity, bonding, earth coupling), impedance analysis at frequencies from 41 Hz to 5 kHz, storage of up to 512 complete measurements, and portability in rugged water-resistant cases. The system operates on batteries, AC power, or 12V DC, prioritizes worker safety by eliminating tower isolation requirements, and offers rapid return on investment for tower testing applications.
| Performance | |
| 3-POINT METHOD Range (Auto-Ranging) | 0.09 Ω to 99.9 kΩ |
| 3-POINT METHOD Resolution | (0.01 to 100) Ω |
| 3-POINT METHOD Accuracy | ± (2 % + 1 ct) |
| 3-POINT METHOD Measurement Frequency | (41 to 5078) Hz |
| 3-POINT METHOD Coupling Measurement | Yes |
| 3-POINT METHOD Auxiliary Rod Resistance Measurement | 0.14 Ω to 99.9 kΩ |
| 3-POINT METHOD Type of Measurement | 3 wires |
| 3-POINT METHOD Measurement Current | > 200 mAAC |
| 4-POINT & SELECTIVE METHODS Range (Auto-Ranging) | 0.011 Ω to 99.99 kΩ |
| 4-POINT & SELECTIVE METHODS Resolution | (0.001 to 10) Ω |
| 4-POINT & SELECTIVE METHODS Accuracy | ± (10 % + 1 ct) |
| 4-POINT & SELECTIVE METHODS Measurement Frequency | Auto: 1611 Hz Manual: (128, 1367, 1611, or 1758) Hz |
| 4-POINT & SELECTIVE METHODS Type of Measurement | 4 wires |
| 4-POINT & SELECTIVE METHODS Measurement Current | > 200 mAAC |
| GROUND MEASUREMENT WITH 2 CLAMPS Range (Auto-Ranging) | (0.1 to 500) Ω |
| GROUND MEASUREMENT WITH 2 CLAMPS Resolution | (0.01 to 1) Ω |
| GROUND MEASUREMENT WITH 2 CLAMPS Accuracy | ± (2 % + 1 ct) |
| GROUND MEASUREMENT WITH 2 CLAMPS Measurement Frequency | (41 to 128) Hz |
| GROUND MEASUREMENT WITH 2 CLAMPS Type of Measurement | 2 clamps |
| GROUND MEASUREMENT WITH 2 CLAMPS Measurement Current | < 26 Arms (w / SR182) < 5 Arms (w / MN82) |
| SOIL RESISTIVITY Range (Auto-Ranging) | 0.01 Ω to 99.9 kΩ |
| SOIL RESISTIVITY Resolution | (0.01 to 100) Ω |
| SOIL RESISTIVITY Accuracy | ± (5 % + 1 ct) |
| SOIL RESISTIVITY Measurement Frequency | (41 to 5078) Hz |
| SOIL RESISTIVITY Type of Measurement | 4 wires |
| SOIL RESISTIVITY Measurement Current | > 200 mAAC |
| GROUND POTENTIAL MEASUREMENT Range (Auto-Ranging) | 0.01 mV to 65 V |
| GROUND POTENTIAL MEASUREMENT Resolution | (0.01 to 10) mV |
| GROUND POTENTIAL MEASUREMENT Accuracy | ± (2 % + 2 cts) |
| GROUND POTENTIAL MEASUREMENT Measurement Frequency | DC |
| GROUND POTENTIAL MEASUREMENT Type of Measurement | 3 wires |
| DC RESISTANCE MEASUREMENT Range (Auto-Ranging) | 0.02 Ω to 99.99 kΩ |
| DC RESISTANCE MEASUREMENT Resolution | 2 wires: (0.01 to 100) Ω 4 wires: (0.001 to 10) Ω |
| DC RESISTANCE MEASUREMENT Accuracy | ± (5 % + 1 ct) |
| DC RESISTANCE MEASUREMENT Auxiliary Rod Resistance Measurement | 0.14 Ω to 99.9 kΩ |
| DC RESISTANCE MEASUREMENT Type of Measurement | 2 or 4 wires |
| DC RESISTANCE MEASUREMENT Measurement Current | > 200 mAAC |
| MEASUREMENTS WITH 6474 Range (Auto-Ranging) | 0.067 Ω to 99.99 kΩ |
| MEASUREMENTS WITH 6474 Resolution | (0.001 to 10) Ω |
| MEASUREMENTS WITH 6474 Accuracy | ± (5 % + 1 ct) |
| MEASUREMENTS WITH 6474 Measurement Frequency | (41 to 5078) Hz |
| MEASUREMENTS WITH 6474 Type of Measurement | GroundFlex® |
| MEASUREMENTS WITH 6474 Measurement Current | > 200 mAAC |
| Power | |
| 3-POINT METHOD No-Load Voltage | (10, 16, 32 or 60) Vrms |
| 4-POINT & SELECTIVE METHODS No-Load Voltage | (10, 16, 32 or 60) Vrms |
| GROUND MEASUREMENT WITH 2 CLAMPS No-Load Voltage | (Not applicable w / 2-clamp method) |
| GROUND POTENTIAL MEASUREMENT No-Load Voltage | ± 16 Vdc |
| DC RESISTANCE MEASUREMENT No-Load Voltage | (10, 16, 32 or 60) Vrms |
| MEASUREMENTS WITH 6474 No-Load Voltage | (10, 16, 32 or 60) Vrms |
| Voltage Interference | Maximum 60 V peak |
| Physical | |
| Dimensions / Weight | (10.7 x 9.84 x 5.04) in (272 x 250 x 128) mm / Model 6472: 7.05 lb (3.2 kg) / Model 6474: 5.07 lb (2.3 kg) |
| Connectivity | |
| Memory / Communication | 512-record memory / Optically isolated USB |
| Other | |
| SOIL RESISTIVITY Soil Resistivity | Wenner and Schlumberger |
| Safety Rating | 50 V CAT IV, complies with IEC 61326-1 / IEC 61010 / IEC 61557-1-4-5 |
Calibration, repair and maintenance for your detection instruments.